Sizing chilled water (CHW) pipes correctly is one of the highest-impact decisions in any hydronic HVAC design. The pipe diameter sets your pump energy, your noise levels and a big part of your installation cost. This guide gives you the chilled water pipe sizing limits from ASHRAE and Carrier, a ready-to-use pipe size chart in GPM and L/s, a step-by-step method with a worked example, and a free Excel sheet and online calculator.

Want the tools right away? Jump to the free Excel download or open the online CHW pipe sizing calculator. Both are free, with no email and no paywall.
What Is Chilled Water Pipe Sizing?
Chilled water pipe sizing is the process of choosing the pipe diameter that carries the required flow from the chiller to the air handling units and fan coil units, while keeping velocity and friction loss (pressure drop) within accepted limits.
Three numbers decide the answer:
- The flow rate required, set by the cooling load (in GPM or L/s).
- The velocity you allow, to control noise and pipe erosion.
- The friction loss you accept per length of pipe, which drives pump head and running cost.
Why Correct CHW Pipe Sizing Matters
- Pump energy. Friction rises roughly with the square of velocity, so one size too small can sharply increase pump power for the same flow.
- Noise. High velocity, especially at valves, sharp turns and size reductions, creates flow noise that carries into occupied spaces.
- Erosion. Sustained high velocity erodes pipe walls and fittings and shortens system life.
- Capital cost. Oversized pipe, insulation, hangers and valves cost more and take up tight ceiling space.
Chilled Water Pipe Sizing Standard (ASHRAE and Carrier)
Most engineers size chilled water pipes against a well-known rule of thumb. It is given in the ASHRAE Handbook – Fundamentals (2017 edition, Chapter 22) as one common recommendation for closed hydronic systems.
| Pipe Size | Sizing Basis |
|---|---|
| 2 in. and below (DN50 and below) | Velocity limit of 4 fps (1.2 m/s) |
| Above 2 in. (above DN50) | Friction loss limit of 4 ft per 100 ft (about 400 Pa/m) |
Small pipes are limited by velocity and larger pipes by friction loss. Beyond this rule of thumb, there are outer limits you should not cross:
- Velocity: minimum 2 fps (0.6 m/s), maximum 15 fps (4.6 m/s).
- Friction loss: minimum 0.75 ft per 100 ft, maximum 10 ft per 100 ft (about 1000 Pa/m).
The minimum velocity matters because chilled water must move fast enough to carry air bubbles to the air vents. Too slow, and air pockets reduce heat transfer at the coils. The maximum velocity guards against erosion. These are design guidelines, so always follow your project specification where it sets different limits.
Chilled Water Pipe Size Chart
The chart below applies the standard directly: pipes 2 in. and smaller are sized to 4 fps, and pipes above 2 in. are sized to 4 ft per 100 ft friction loss. It is for Schedule 40 steel pipe and chilled water.

Use the table for a fast first pick, then confirm with the calculator.
| Nominal Size | Sizing Basis | Max Flow (GPM) | Max Flow (L/s) | Velocity (fps) | Velocity (m/s) |
|---|---|---|---|---|---|
| 1/2 in. (DN15) | 4 fps | 4 | 0.2 | 4.0 | 1.2 |
| 3/4 in. (DN20) | 4 fps | 7 | 0.4 | 4.0 | 1.2 |
| 1 in. (DN25) | 4 fps | 11 | 0.7 | 4.0 | 1.2 |
| 1 1/4 in. (DN32) | 4 fps | 19 | 1.2 | 4.0 | 1.2 |
| 1 1/2 in. (DN40) | 4 fps | 25 | 1.6 | 4.0 | 1.2 |
| 2 in. (DN50) | 4 fps | 42 | 2.6 | 4.0 | 1.2 |
| 2 1/2 in. (DN65) | 4 ft/100 ft | 73 | 4.6 | 4.9 | 1.5 |
| 3 in. (DN80) | 4 ft/100 ft | 130 | 8.2 | 5.7 | 1.7 |
| 4 in. (DN100) | 4 ft/100 ft | 268 | 16.9 | 6.7 | 2.0 |
| 5 in. (DN125) | 4 ft/100 ft | 487 | 30.7 | 7.8 | 2.4 |
| 6 in. (DN150) | 4 ft/100 ft | 791 | 49.9 | 8.8 | 2.7 |
| 8 in. (DN200) | 4 ft/100 ft | 1629 | 102.8 | 10.4 | 3.2 |
| 10 in. (DN250) | 4 ft/100 ft | 2963 | 186.9 | 12.1 | 3.7 |
| 12 in. (DN300) | 4 ft/100 ft | 4755 | 300.0 | 13.5 | 4.1 |
Velocity stays under the 15 fps ceiling across the whole range, and larger pipes run faster while holding the same friction rate. To read the chart image: find your flow on the bottom axis, go up to the pipe size line, then check the friction loss on the left axis and the velocity on the blue lines. Keep your point inside the green design band.
How to Size a Chilled Water Pipe (Step by Step)
- Find the design flow. In US units, a 10°F delta-T gives about 2.4 GPM per ton. In metric, flow in L/s = cooling load in kW ÷ (4.19 × delta-T in °C).
- Apply the standard. For pipes 2 in. and below, target 4 fps. For pipes above 2 in., target 4 ft per 100 ft.
- Pick a trial size from the pipe size chart above.
- Check velocity and friction for that size with the calculator. If either is above your target, go up one size. If both are very low, you may be able to go down a size.
- Repeat for each segment. Mains carry more flow than branches, so the diameter steps down toward the terminals.
- Confirm pump head. Add the friction of the longest (index) run plus fittings and equipment to set the pump duty.
Worked Example: 350 kW (100 TR) Branch
A chilled water branch serves 350 kW of cooling load, about 100 TR, with a delta-T of 5.5°C. The pipe is Schedule 40 steel.
| Step | Result |
|---|---|
| Design flow | 350 ÷ (4.19 × 5.5) = 15.2 L/s (about 241 GPM) |
| 3 in. (DN80) | Chart limit is 8.2 L/s. Too small |
| 4 in. (DN100) | Chart limit is 16.9 L/s. Accepted |
| Velocity in 4 in. | About 6.1 fps (1.85 m/s) |
| Friction loss in 4 in. | About 3.3 ft per 100 ft (about 320 Pa/m) |
Both values are inside the limits, so DN100 is suitable for this branch.
Recommended Velocity by Service (Carrier)
The 4 fps and 4 ft per 100 ft rule of thumb is a starting point. The Carrier System Design Manual (Part 3, Piping Design) recommends different velocity bands for different parts of the system.
| Service | Velocity (fps) | Velocity (m/s) |
|---|---|---|
| Pump discharge | 8 to 12 | 2.4 to 3.7 |
| Pump suction | 4 to 7 | 1.2 to 2.1 |
| Header | 4 to 15 | 1.2 to 4.6 |
| Riser | 3 to 10 | 0.9 to 3.0 |
Erosion also depends on how many hours per year the system runs. Carrier ties the maximum velocity to operating hours: pipes in use about 8,000 hours per year should stay near 8 fps, while pipes in use about 1,500 hours per year can go up to 15 fps. Chilled water plants in the Gulf often run most of the year, so the lower end is the safer choice. Keep pump suction velocity low to protect against cavitation.
Friction Loss and the Cost Trade-Off
Friction loss (also called pressure drop or head loss) is a cost decision:
- Lower friction loss means a bigger pipe: higher material, insulation and labour cost, but lower pump energy for the life of the system.
- Higher friction loss means a smaller pipe: cheaper to install, but more pump energy every year.
The cost difference between small pipe sizes is modest, so it pays to size small pipes (below 4 in.) to a lower friction loss and save pumping energy. For large pipes (4 in. and above), material and insulation cost climbs steeply, so a higher friction loss is more economical, with about 10 ft per 100 ft as the usual upper limit.
Two site factors also push toward smaller pipe where possible: large pipes are harder to handle and may need lifting equipment, and the ceiling void is often too tight for very large diameters. An owner-operated building, on the other hand, often justifies a lower friction loss, because the energy saving benefits the owner for years.
Pipe Material and Schedule
Steel (Schedule 40), copper (Type K, L, M) and plastics (PVC, ABS) have different inside diameters and roughness for the same nominal size, so the same flow gives a different velocity and friction in each. Select the exact material and schedule in the calculator instead of assuming one.
Practical Notes
| Mistake | What Happens | What to Do |
|---|---|---|
| Sizing only to “what fits the flow” | Pump head becomes inconsistent across the system | Apply one sizing standard to every segment |
| One velocity limit everywhere | Suction lines end up too fast, or headers too large | Use the band for each service: suction, discharge, header and riser |
| Velocity below 2 fps (0.6 m/s) | Air pockets collect and coil performance drops | Go down one size, or accept it only on short low-flow branches |
| Forgetting fittings | Pump head is underestimated | Add the equivalent length of elbows, tees, valves and strainers |
| Mixing up schedules | Wrong inside diameter, so wrong velocity | Check Sch 40, Sch 80 or copper type before you read the result |
Online Chilled Water Pipe Calculators
Prefer instant results in the browser? Use either tool:
- CHW Pipe Sizing Calculator: enter the cooling load (TR or kW) and delta-T, or the flow, and it selects the pipe size and gives velocity, friction loss and total head loss for the run.
- Chilled Water Pipe Calculator: pick the pipe type, size and fluid, enter the flow, and read velocity, Reynolds number, friction factor and head loss.
Prefer the classic desktop tool? Get the McQuay Pipe Sizer free download.
Download Chilled Water Pipe Sizing Excel
- File Name: MEPBase_PipeSizer.xlsx
- File Type: Excel sheet (.xlsx)
- Units: US or SI
- Inputs: pipe type, pipe size, fluid and flow
- Results: velocity, Reynolds number, friction factor, head loss, elbow loss and pipe properties
- Usage: Free, no sign-up
Click below to download the Excel sheet. The link will appear after a short wait.
Checking…
Related Downloads
- McQuay Pipe Sizer v6.2 Free Download
- McQuay Duct Sizer v6.4 Free Download
- Carrier HAP: Official Free Trial and v6 Guide
- Psychrometric Chart PDF Free Download
- All MEP Software
Frequently Asked Questions
What is the chilled water pipe sizing standard?
The common rule of thumb is a velocity limit of 4 fps (1.2 m/s) for pipes 2 in. and below, and a friction loss limit of 4 ft per 100 ft (about 400 Pa/m) for pipes above 2 in. The outer limits are 2 to 15 fps for velocity and 0.75 to 10 ft per 100 ft for friction loss.
What velocity is recommended for chilled water pipes?
Keep velocity between 2 fps (to carry air) and 15 fps (to limit erosion). Carrier suggests 8 to 12 fps for pump discharge, 4 to 7 fps for pump suction, 4 to 15 fps for headers and 3 to 10 fps for risers.
How do I calculate chilled water flow from the cooling load?
In metric, flow in L/s = cooling load in kW ÷ (4.19 × delta-T in °C). In US units, a 10°F delta-T gives about 2.4 GPM per ton.
How do I calculate chilled water pipe size?
Start from the design flow, apply the standard (4 fps for 2 in. and below, 4 ft per 100 ft above 2 in.), pick a trial size from the chart, then confirm velocity and friction with a calculator and adjust the size up or down.
What friction loss should I use for chilled water?
Stay within 0.75 to 10 ft per 100 ft. Use a lower friction loss for small pipes (below 4 in.) to save pump energy, and a higher friction loss for large pipes (4 in. and above) to save installation cost.
Can I size chilled water pipes in Excel?
Yes. The free chilled water pipe sizing Excel on this page lets you select pipe material, schedule, size and fluid, then gives velocity, friction loss and pipe properties in US or SI units.
What is the McQuay pipe sizer?
It is a long-standing Windows tool for hydronic pipe sizing. You can get it on the McQuay Pipe Sizer page.
Need another HVAC chart or a fix in this file? Leave a comment below. Stay connected with MEPBase.com for more MEP software, DWG files and free calculators.


