McQuay Pipe Sizer is free HVAC pipe sizing software for chilled water and other hydronic systems. Enter the flow rate, pick the pipe and the fluid, and it shows the water velocity and the head loss, so you can confirm a pipe size in seconds. On this page you can download McQuay Pipe Sizer v6.2 (also written as PipeSizer), follow a worked example, and find an online option for when you cannot run software.
It is made for HVAC design engineers and MEP draftsmen who size chilled water, condenser water and heating pipes for design drawings, shop drawings and pump head calculations.

File Information
- Software Name: McQuay DesignTools PipeSizer
- Version: 6.2
- Developer: McQuay International (now Daikin Applied)
- File Type: Windows program
- Units: US units (USgpm, ft/s, ft/100 ft)
- Language: English
- Usage: Free
What McQuay Pipe Sizer Does
- Checks a pipe size against the flow: shows fluid velocity, Reynolds number, friction factor and head loss in ft per 100 ft.
- Gives the pipe data: outside diameter, wall thickness, inside diameter, inside area and weight of pipe, empty and full of fluid.
- Handles different pipes and fluids: both are chosen from drop-down lists, for example Sch 40 Steel pipe with 50°F Water for chilled water.
- Shows elbow loss: the head loss through an elbow at the same flow, in ft.
- Replaces chart reading: no friction chart and no manual Darcy-Weisbach calculation.
How to Use McQuay Pipe Sizer
- Select the pipe type from the first drop-down list, for example Sch 40 Steel.
- Select the nominal size from the list below it.
- Select the fluid from the list on the right. Keep 50°F Water for chilled water.
- Type the flow rate in USgpm. If your design is in L/s, multiply by 15.85.
- Read Fluid velocity and Head Loss. Compare both with your project limits.
- Adjust the size. If the velocity or head loss is too high, pick the next size up and check again.
Use Print to print the result for your calculation file.
Reading the Screen: 1/2 in. Pipe at 1.4 USgpm
The screenshot above shows a 1/2 in. Sch 40 steel pipe carrying 1.4 USgpm of 50°F water. These are the values the tool gives.
| Item | Value | Source |
|---|---|---|
| Pipe | Sch 40 Steel, 1/2 in. | You select |
| Fluid | 50°F Water | You select |
| Flow rate | 1.4 USgpm (about 0.09 L/s) | You type |
| Inside diameter | 0.622 in. (15.8 mm) | Tool |
| Fluid velocity | 1.48 ft/s (0.45 m/s) | Tool |
| Reynolds number | 5,436 | Tool |
| Friction factor | 0.03972 | Tool |
| Head loss | 2.602 ft/100 ft (about 255 Pa/m) | Tool |
| Elbow loss | 0.068 ft | Tool |
Sizing Example: 35 L/s Chilled Water Pipe
A chilled water branch carries 35 L/s, which is about 555 USgpm. The project limits the velocity to 2.3 m/s. The pipe is Schedule 40 steel.
D = √(4Q / πV), where D is the inside diameter in m, Q is the flow in m³/s and V is the velocity in m/s.
| Step | Result |
|---|---|
| Flow rate | 35 L/s = 0.035 m³/s (about 555 USgpm) |
| Minimum inside diameter at 2.3 m/s | 139 mm |
| DN125 (5 in.), inside diameter 128.2 mm | 2.71 m/s. Too high |
| DN150 (6 in.), inside diameter 154.1 mm | 1.88 m/s (about 6.2 ft/s). Accepted |
| Head loss in DN150 | About 2 ft per 100 ft (about 200 Pa/m) |
The head loss here is an approximate hand calculation with the Darcy-Weisbach equation. To confirm it, select Sch 40 Steel and 6 in. in the tool and type 555 USgpm.
Typical Design Values
The values below are typical starting points only. Always follow your project specification and the consultant’s design criteria.
| Parameter | Typical Value |
|---|---|
| Pipes 2 in. (DN50) and smaller | Velocity up to 4 ft/s (1.2 m/s) |
| Pipes above 2 in. | Head loss up to 4 ft per 100 ft (about 400 Pa/m) |
| Minimum velocity | About 2 ft/s (0.6 m/s), so that air is carried to the vents |
For the full table and pipe size chart, see our chilled water pipe sizing guide.
Working in metric? Most Gulf project specifications use L/s and Pa/m. Multiply L/s by 15.85 to get USgpm, and m/s by 3.28 to get ft/s. A head loss of 1 ft per 100 ft is about 98 Pa/m.
Practical Notes
| Point | Why It Matters | What to Do |
|---|---|---|
| Straight pipe only | The head loss is per length of straight pipe. Fittings and valves are extra | Add elbows, tees, strainers, balancing valves and coil losses before you fix the pump head |
| Oversizing “to be safe” | Low velocity lets air collect and adds pipe, insulation and support cost | Keep the velocity above the minimum and size to the limit, not far below it |
| Inside diameter | Nominal size is not the inside diameter, and it changes with schedule and material | Select the correct pipe type before you read the result |
| Fluid selection | Head loss changes with the fluid and its temperature | Select the fluid that matches your system before you read the result |
| Pump selection | Pipe size and pump head move together | Recheck the pump duty point after any pipe size change |
Online Pipe Sizer (No Download)
McQuay Pipe Sizer is a Windows program, so it will not run on a phone, a tablet or a Mac. For a quick check without downloading anything, use our free online chilled water pipe calculator. It works in US and metric units, covers steel, copper and plastic pipe, and includes water and glycol mixes.
Download McQuay Pipe Sizer
Click below to download McQuay Pipe Sizer. The link will appear after a short wait.
Checking…
If the file comes as a zip, extract it first and then run the program.
Related Downloads
- McQuay Duct Sizer v6.4 Free Download
- Chilled Water Pipe Sizing Chart and Calculator
- Carrier HAP: Free Trial and v6 Guide
- Psychrometric Chart PDF Free Download
- All MEP Software
Frequently Asked Questions
Is McQuay Pipe Sizer free?
Yes. It is a free pipe sizing tool originally developed by McQuay International, now Daikin Applied. You do not need a licence key or registration.
What is McQuay Pipe Sizer used for?
It is used to size HVAC water pipes. You select the pipe and fluid and type the flow rate, and it shows the velocity and head loss for that pipe size.
What is the latest version of McQuay Pipe Sizer?
Version 6.2 is the version offered on this page.
Can I use McQuay Pipe Sizer with SI units?
No. Version 6.2 works in US units only: USgpm, ft/s and ft per 100 ft. Multiply L/s by 15.85 to enter the flow. To work fully in L/s, m/s and Pa/m, use the online chilled water pipe calculator linked above.
What velocity should I use for chilled water pipes?
A typical starting point is up to 4 ft/s (1.2 m/s) for pipes 2 in. and smaller, and a head loss limit of 4 ft per 100 ft for larger pipes. Your project specification may require different values.
Is there an online version of McQuay Pipe Sizer?
There is no official online version. For browser-based sizing, use the free MEPBase online chilled water pipe calculator.
Does the head loss include fittings and valves?
No. The head loss is for straight pipe. The tool also shows an elbow loss figure, but you still need to add the losses of all fittings, valves and equipment when you calculate the pump head.
Need another HVAC tool or a fix in this file? Leave a comment below. Stay connected with MEPBase.com for more MEP software, DWG files and AutoCAD add-ons.