<?xml version="1.0" encoding="UTF-8"?><rss version="2.0"
	xmlns:content="http://purl.org/rss/1.0/modules/content/"
	xmlns:wfw="http://wellformedweb.org/CommentAPI/"
	xmlns:dc="http://purl.org/dc/elements/1.1/"
	xmlns:atom="http://www.w3.org/2005/Atom"
	xmlns:sy="http://purl.org/rss/1.0/modules/syndication/"
	xmlns:slash="http://purl.org/rss/1.0/modules/slash/"
	>

<channel>
	<title>feed water pump &#8211; MEPBase</title>
	<atom:link href="https://mepbase.com/tag/feed-water-pump/feed/" rel="self" type="application/rss+xml" />
	<link>https://mepbase.com</link>
	<description>Free MEP CAD Blocks, DWG Drawings and Tools</description>
	<lastBuildDate>Sun, 11 Oct 2026 19:39:56 +0000</lastBuildDate>
	<language>en-US</language>
	<sy:updatePeriod>
	hourly	</sy:updatePeriod>
	<sy:updateFrequency>
	1	</sy:updateFrequency>
	<generator>https://wordpress.org/?v=7.1.5</generator>

<image>
	<url>https://mepbase.com/wp-content/uploads/2026/06/cropped-mepbase-icon-512-32x32.png</url>
	<title>feed water pump &#8211; MEPBase</title>
	<link>https://mepbase.com</link>
	<width>32</width>
	<height>32</height>
</image> 
	<item>
		<title>Boiler Feed Pump Calculation: Flow, Head &#038; Motor Power</title>
		<link>https://mepbase.com/boiler-feed-pump-calculation/</link>
					<comments>https://mepbase.com/boiler-feed-pump-calculation/#respond</comments>
		
		<dc:creator><![CDATA[MEPbase Staff]]></dc:creator>
		<pubDate>Fri, 10 Jul 2026 15:58:45 +0000</pubDate>
				<category><![CDATA[HVAC]]></category>
		<category><![CDATA[boiler feed pump]]></category>
		<category><![CDATA[boiler feed pump calculation]]></category>
		<category><![CDATA[feed water pump]]></category>
		<category><![CDATA[mechanical engineering]]></category>
		<category><![CDATA[motor power calculation]]></category>
		<category><![CDATA[multistage pump]]></category>
		<category><![CDATA[NPSH]]></category>
		<category><![CDATA[pump head calculation]]></category>
		<category><![CDATA[pump sizing]]></category>
		<category><![CDATA[steam boiler]]></category>
		<guid isPermaLink="false">https://mepbase.com/?p=688</guid>

					<description><![CDATA[Sizing a boiler feed pump looks simple on paper — until an undersized pump can&#8217;t hold drum level on a live boiler, ... <a title="Boiler Feed Pump Calculation: Flow, Head &#038; Motor Power" class="read-more" href="https://mepbase.com/boiler-feed-pump-calculation/" aria-label="Read more about Boiler Feed Pump Calculation: Flow, Head &#038; Motor Power">Read more</a>]]></description>
										<content:encoded><![CDATA[<figure id="attachment_689" aria-describedby="caption-attachment-689" style="width: 1190px" class="wp-caption aligncenter"><img fetchpriority="high" decoding="async" class="size-full wp-image-689" src="https://mepbase.com/wp-content/uploads/2026/07/boiler-feed-pump-calculation-diagram.jpg" alt="Boiler feed pump sizing diagram showing feed tank, multistage pump, economizer and steam boiler with flow, head and power formulas" width="1200" height="675" srcset="https://mepbase.com/wp-content/uploads/2026/07/boiler-feed-pump-calculation-diagram.jpg 1200w, https://mepbase.com/wp-content/uploads/2026/07/boiler-feed-pump-calculation-diagram-300x169.jpg 300w, https://mepbase.com/wp-content/uploads/2026/07/boiler-feed-pump-calculation-diagram-1024x576.jpg 1024w, https://mepbase.com/wp-content/uploads/2026/07/boiler-feed-pump-calculation-diagram-768x432.jpg 768w, https://mepbase.com/wp-content/uploads/2026/07/boiler-feed-pump-calculation-diagram-390x220.jpg 390w" sizes="(max-width: 1200px) 100vw, 1200px" /><figcaption id="caption-attachment-689" class="wp-caption-text">Boiler feed pump system — the pump must overcome boiler pressure, economizer ΔP, static head and friction losses.</figcaption></figure>
<p>Sizing a <strong>boiler feed pump</strong> looks simple on paper — until an undersized pump can&#8217;t hold drum level on a live boiler, or an oversized one runs throttled and cavitating for years. This guide walks through the complete <strong>boiler feed pump calculation</strong> step by step: feedwater flow rate, total pump head, NPSH check and motor power — with formulas, a fully worked example, a feedwater property table and a quick sizing table.</p>
<div style="border-left: 5px solid #00856f; background: #eef7f5; padding: 16px 20px; margin: 20px 0;"><strong>Boiler feed pump calculation in short:</strong></p>
<ol style="margin: 8px 0 0;">
<li><strong>Flow:</strong> Q = boiler evaporation × 1.15–1.25 ÷ water density</li>
<li><strong>Head:</strong> discharge pressure at safety-valve set pressure + 3% + economizer/valve ΔP, converted to metres, plus static height and friction</li>
<li><strong>NPSH:</strong> NPSH available must exceed the pump&#8217;s NPSH required by 0.5–1 m</li>
<li><strong>Power:</strong> kW = ρ × g × Q × H ÷ (3.6 × 10⁶ × η), then the next standard motor size</li>
</ol>
</div>
<p>💡 <strong>Short on time?</strong> Use the free <a title="Boiler Feed Pump Calculator" href="https://tools.mepbase.com/boiler-feed-pump-calculator"><strong>Boiler Feed Pump Calculator</strong></a> — enter boiler capacity and pressure, get flow, head and motor kW instantly.</p>
<h2>What Is a Boiler Feed Pump?</h2>
<p>A boiler feed pump (also called a <em>feed water pump</em> or BFW pump) delivers treated water from the feed tank or deaerator into a steam boiler <em>against</em> the boiler&#8217;s operating pressure. Because it must overcome full boiler pressure plus system losses, it is a <strong>high-head, moderate-flow duty</strong> — which is why <a href="https://en.wikipedia.org/wiki/Boiler_feedwater_pump" target="_blank" rel="nofollow noopener">multistage centrifugal pumps</a> are the industry standard for this application.</p>
<p>Correct sizing matters more here than in almost any other pump application. Boiler codes such as ASME Section I, EN 12953-6 and the Indian Boiler Regulations require the feed apparatus to deliver <em>more</em> water than the boiler can evaporate at peak, usually with a second, independent means of feeding — because losing drum level on a fired boiler is a genuine safety event, not just an inconvenience.</p>
<h2>Boiler Feed Pump Calculation — 4 Steps</h2>
<h3>Step 1: Feedwater Flow Rate</h3>
<p>The pump must supply more than the boiler&#8217;s maximum evaporation to cover blowdown losses, on/off or modulating feed control, and safety-valve lift conditions. Standard practice is a <strong>15–25% margin</strong>:</p>
<pre><strong>Q (kg/hr) = Boiler Evaporation × (1 + Margin%)

Q (m³/hr) = Q (kg/hr) ÷ ρ</strong>

where ρ = water density at feedwater temperature (kg/m³)</pre>
<p>Don&#8217;t skip the density correction. Feedwater at 85–105 °C has a density of roughly 955–970 kg/m³, not 1000 — about a 3–4% difference in volumetric flow. Use the feedwater table further down for exact values.</p>
<h3>Step 2: Discharge Pressure and Total Head</h3>
<p>Size the pump for the worst case: the boiler sitting at its <strong>safety-valve set pressure</strong>, plus safety-valve accumulation (typically 3%), plus the pressure drop across the economizer, feed control valve and check valve. With on/off feed control the pump must still put water in at this pressure — normal working pressure is not the design point.</p>
<pre><strong>P<sub>dis</sub> (bar g) = P<sub>SV set</sub> × 1.03 + ΔP<sub>economizer + valves</sub></strong></pre>
<p>Pump head is the <em>difference</em> between where the water ends up and where it starts. Taking the feed tank water surface as the start and the boiler feed inlet as the end:</p>
<pre><strong>H (m) = (P<sub>dis</sub> − P<sub>tank</sub>) × 10⁵ ÷ (ρ × 9.81) + (z<sub>boiler inlet</sub> − z<sub>tank level</sub>) + h<sub>f</sub></strong>

P<sub>tank</sub> = feed tank pressure, bar g (0 for a vented tank, about 0.2–0.3 for a pressurised deaerator)
z = elevations in m, h<sub>f</sub> = total suction + discharge pipe friction in m</pre>
<p>Two points engineers often miss: a pressurised deaerator <em>reduces</em> the pump head (its pressure is already on the suction side), and a feed tank mounted high above the pump does the same through the elevation term.</p>
<p><strong>Rule of thumb:</strong> 1 bar ≈ 10.2 m of water head with cold water. With hot feedwater the lower density pushes this to about 10.5–10.7 m per bar.</p>
<h3>Step 3: NPSH Check — the Step Most Calculations Skip</h3>
<p>Hot feedwater sits close to its boiling point, so the pressure at the pump suction only needs to drop a little before the water flashes and the pump <a href="https://en.wikipedia.org/wiki/Cavitation" target="_blank" rel="nofollow noopener">cavitates</a>. Check the net positive suction head available:</p>
<pre><strong>NPSH<sub>a</sub> (m) = (P<sub>surface</sub> − P<sub>vapour</sub>) ÷ (ρ × g) + H<sub>s</sub> − h<sub>f,suction</sub></strong>

P<sub>surface</sub> = absolute pressure on the tank water surface (Pa)
P<sub>vapour</sub> = vapour pressure of water at feedwater temperature (Pa)
H<sub>s</sub> = height of tank water level above pump centreline (m)</pre>
<p>The result changes completely depending on the type of tank:</p>
<ul>
<li><strong>Vented feed tank at 85 °C:</strong> the surface is at atmospheric pressure (101.3 kPa) and the vapour pressure is 57.9 kPa, so the pressure term alone gives about <strong>4.6 m</strong> of NPSH before any elevation is added.</li>
<li><strong>Deaerator at saturation (e.g. 105 °C):</strong> the water is at its boiling point, so surface pressure equals vapour pressure and the pressure term is <strong>zero</strong>. All the NPSH has to come from elevation: NPSH<sub>a</sub> = H<sub>s</sub> − h<sub>f,suction</sub>.</li>
</ul>
<p>That second case is exactly why deaerators are mounted on a structure several metres above the feed pumps. Keep NPSH<sub>a</sub> at least <strong>0.5–1 m above the pump&#8217;s NPSH<sub>r</sub></strong> at the duty point, and check it again at the end of the curve where NPSH<sub>r</sub> rises. If the site is well above sea level, use the local atmospheric pressure, not 101.3 kPa.</p>
<h3>Step 4: Pump Power and Motor Selection</h3>
<pre><strong>P<sub>hydraulic</sub> (kW) = ρ × g × Q × H ÷ (3.6 × 10⁶)

P<sub>shaft</sub> = P<sub>hydraulic</sub> ÷ η<sub>pump</sub>

Motor kW = next standard IEC rating ≥ P<sub>shaft</sub> × (1 + service factor)</strong></pre>
<p>Small multistage pumps at high-head, low-flow feed duty typically run at <strong>35–65% efficiency</strong> — well below the 70–80% common for larger HVAC pumps. Always check the manufacturer&#8217;s curve. A 10–20% motor margin over shaft power is normal practice.</p>
<h2>Worked Example: 5 TPH Boiler, Safety Valve Set at 10.5 bar g</h2>
<p>Feed pump for a 5,000 kg/hr boiler with the safety valve set at 10.5 bar g. Vented feed tank, feedwater at 85 °C, 25% flow margin, 3% accumulation, 1 bar economizer/valve drop. The tank water level is 4 m above the pump centreline and the boiler feed inlet 9 m above it (5 m net static height). Total pipe friction 5 m, of which 0.5 m is on the suction side.</p>
<ol>
<li><strong>Flow:</strong> 5,000 × 1.25 = 6,250 kg/hr → at ρ = 968.6 kg/m³ → <strong>6.45 m³/hr</strong></li>
<li><strong>Discharge pressure:</strong> 10.5 × 1.03 + 1.0 = <strong>11.8 bar g</strong></li>
<li><strong>Head:</strong> 11.8 × 10⁵ ÷ (968.6 × 9.81) = 124.3 m, + 5 m static + 5 m friction = <strong>≈ 134 m</strong></li>
<li><strong>NPSH available:</strong> (101,325 − 57,870) ÷ (968.6 × 9.81) = 4.6 m, + 4 m − 0.5 m = <strong>≈ 8.1 m</strong>. A small multistage pump with NPSH<sub>r</sub> of 1–3 m at this duty has a comfortable margin. With a deaerator at 105 °C and the same layout, NPSH<sub>a</sub> would be only 4 − 0.5 = 3.5 m.</li>
<li><strong>Power:</strong> hydraulic ≈ 2.3 kW → at 45% efficiency, shaft ≈ 5.1 kW → with 15% margin ≈ 5.9 kW → <strong>select a 7.5 kW (10 HP) motor</strong></li>
</ol>
<p>You can check the flow, head and motor numbers in seconds with the <a href="https://tools.mepbase.com/boiler-feed-pump-calculator">online boiler feed pump calculator</a> — it applies the density correction and IEC motor selection automatically. For the suction side, the <a href="https://tools.mepbase.com/water-pump-npsh-calculator">NPSH calculator</a> works through the same check.</p>
<h2>Feedwater Properties by Temperature</h2>
<table style="border-collapse: collapse; width: 100%;" border="1" cellpadding="8">
<thead>
<tr style="background-color: #00856f; color: #ffffff;">
<th>Feedwater temp.</th>
<th>Density (kg/m³)</th>
<th>Vapour pressure (kPa abs)</th>
<th>Head per bar (m)</th>
</tr>
</thead>
<tbody>
<tr>
<td>60 °C</td>
<td>983.2</td>
<td>19.9</td>
<td>10.37</td>
</tr>
<tr>
<td>70 °C</td>
<td>977.8</td>
<td>31.2</td>
<td>10.43</td>
</tr>
<tr>
<td>80 °C</td>
<td>971.8</td>
<td>47.4</td>
<td>10.49</td>
</tr>
<tr>
<td>85 °C</td>
<td>968.6</td>
<td>57.9</td>
<td>10.52</td>
</tr>
<tr>
<td>90 °C</td>
<td>965.3</td>
<td>70.2</td>
<td>10.56</td>
</tr>
<tr>
<td>95 °C</td>
<td>961.9</td>
<td>84.6</td>
<td>10.60</td>
</tr>
<tr>
<td>100 °C</td>
<td>958.4</td>
<td>101.4</td>
<td>10.64</td>
</tr>
<tr>
<td>105 °C</td>
<td>954.7</td>
<td>120.9</td>
<td>10.68</td>
</tr>
</tbody>
</table>
<p><em>Saturated water properties. Above about 100 °C the vapour pressure exceeds atmospheric, which is why such water can only be held in a pressurised deaerator.</em></p>
<h2>Quick Reference: Feed Pump Sizes for Common Boilers</h2>
<table style="border-collapse: collapse; width: 100%;" border="1" cellpadding="8">
<thead>
<tr style="background-color: #00856f; color: #ffffff;">
<th>Boiler capacity</th>
<th>Pump flow (1.25×)</th>
<th>Pump head</th>
<th>Shaft power @ 45%</th>
<th>Motor</th>
</tr>
</thead>
<tbody>
<tr>
<td>1,000 kg/hr (1 TPH)</td>
<td>1.3 m³/hr</td>
<td>≈ 129 m</td>
<td>1.0 kW</td>
<td>1.5 kW</td>
</tr>
<tr>
<td>2,000 kg/hr (2 TPH)</td>
<td>2.6 m³/hr</td>
<td>≈ 129 m</td>
<td>2.0 kW</td>
<td>3 kW</td>
</tr>
<tr>
<td>5,000 kg/hr (5 TPH)</td>
<td>6.5 m³/hr</td>
<td>≈ 129 m</td>
<td>4.9 kW</td>
<td>7.5 kW</td>
</tr>
<tr>
<td>10,000 kg/hr (10 TPH)</td>
<td>12.9 m³/hr</td>
<td>≈ 129 m</td>
<td>9.8 kW</td>
<td>15 kW</td>
</tr>
<tr>
<td>20,000 kg/hr (20 TPH)</td>
<td>25.8 m³/hr</td>
<td>≈ 129 m</td>
<td>19.5 kW</td>
<td>30 kW</td>
</tr>
</tbody>
</table>
<p><em>Indicative values: safety valve set at 10 bar g, 85 °C vented feed tank, 1 bar economizer/valve drop, 10 m static + friction, 45% pump efficiency and 15% motor margin. The smallest pumps often run below 45% efficiency, so check whether the next motor size up is needed. Always verify against vendor curves.</em></p>
<h2>5 Design Tips Engineers Learn the Hard Way</h2>
<p><strong>1. NPSH is the #1 failure point.</strong> Elevate the deaerator or feed tank 3–8 m above the pump centreline, keep suction piping short with few fittings and one size larger than the pump suction nozzle, and avoid strainers that clog unnoticed on the suction side. Run the NPSH check in Step 3 for the hottest feedwater the tank will ever see.</p>
<p><strong>2. Provide standby capacity.</strong> Boiler codes generally require two independent means of feeding. The standard arrangement is 2 × 100% pumps (one duty, one standby), each able to meet the full feed requirement on its own.</p>
<p><strong>3. Design at the safety-valve condition.</strong> With on/off feed control, the pump must deliver water while the boiler sits at safety-valve set pressure — use that, not the working pressure, as the design point.</p>
<p><strong>4. Protect against minimum flow.</strong> Multistage pumps overheat quickly at low or zero flow, especially with hot water. Provide a recirculation line, leak-off orifice or automatic recirculation valve back to the feed tank, sized to the pump&#8217;s minimum continuous flow.</p>
<p><strong>5. Verify with the vendor curve.</strong> Hand calculations and calculators give a preliminary duty point. Final selection must match a manufacturer&#8217;s tested performance curve (Grundfos CR, KSB Movitec, Wilo MVI, Kirloskar and similar ranges), including NPSH<sub>r</sub> at the duty point.</p>
<h2>Frequently Asked Questions</h2>
<h3>How do you calculate boiler feed pump capacity?</h3>
<p>Multiply the boiler&#8217;s maximum evaporation rate by 1.15–1.25, then divide by water density at feedwater temperature to convert kg/hr to m³/hr. The margin covers blowdown, feed-control cycling and safety-valve lift.</p>
<h3>How much head does a boiler feed pump need?</h3>
<p>Take the safety-valve set pressure plus about 3% accumulation, add the economizer and feed-valve pressure drops, subtract any pressure in the feed tank or deaerator, and convert to metres of water (about 10.2–10.7 m per bar depending on temperature). Then add the static height from tank level to boiler inlet and the pipe friction.</p>
<h3>Why is the feed pump sized at 1.25 × evaporation?</h3>
<p>Because the pump must refill the boiler faster than steam leaves it, replace blowdown water, and hold drum level even while the safety valve is lifting. Boiler codes require feed capacity above peak evaporation.</p>
<h3>How do you calculate NPSH for a boiler feed pump?</h3>
<p>NPSH available = (absolute pressure on the tank surface − vapour pressure at feedwater temperature) ÷ (ρ × g), plus the height of the water level above the pump, minus suction pipe friction. For a deaerator at saturation the pressure term is zero, so the NPSH comes only from elevation.</p>
<h3>What type of pump is used for boiler feed water?</h3>
<p>Vertical or horizontal multistage centrifugal pumps, because of the high head requirement. Typical efficiency at small feed duties is 35–65%. Very small boilers sometimes use regenerative turbine pumps.</p>
<h3>What is the formula for pump motor power?</h3>
<p>P (kW) = ρ × g × Q × H ÷ (3.6 × 10⁶ × η), where Q is in m³/hr, H in metres, ρ in kg/m³ and η is pump efficiency as a decimal. Then select the next standard IEC motor rating above P × (1 + service factor).</p>
<h2>Calculate Your Feed Pump in Seconds</h2>
<p>Skip the manual arithmetic — the free tool does the complete calculation with automatic density correction, unit conversion (kg/hr, TPH, lb/hr, bar, psi, kg/cm²) and standard IEC motor selection:</p>
<p>👉 <a href="https://tools.mepbase.com/boiler-feed-pump-calculator"><strong>Open the Boiler Feed Pump Calculator →</strong></a></p>
<p>Related free pump tools on MEPBase: <a href="https://tools.mepbase.com/water-pump-npsh-calculator">Pump NPSH Calculator</a>, <a href="https://tools.mepbase.com/pump-head-calculator">Pump Head Calculator</a>, <a href="https://tools.mepbase.com/pump-horsepower-calculator">Pump Horsepower Calculator</a> and <a href="https://tools.mepbase.com/bar-to-psi">Bar to PSI Converter</a>.</p>
<h2>References</h2>
<ul>
<li><a href="https://en.wikipedia.org/wiki/Boiler_feedwater_pump" target="_blank" rel="nofollow noopener">Boiler feedwater pump — Wikipedia</a></li>
<li><a href="https://en.wikipedia.org/wiki/Net_positive_suction_head" target="_blank" rel="nofollow noopener">Net positive suction head (NPSH) — Wikipedia</a></li>
<li><a href="https://www.spiraxsarco.com/learn-about-steam" target="_blank" rel="nofollow noopener">Spirax Sarco — Steam Engineering Principles (Feedwater Systems)</a></li>
<li>ASME Boiler and Pressure Vessel Code, Section I — Power Boilers (feedwater supply)</li>
<li>EN 12953-6 — Shell Boilers: Requirements for Equipment for the Boiler</li>
<li>Indian Boiler Regulations, 1950 — feed apparatus requirements</li>
<li>IAPWS-IF97 — properties of water and steam (feedwater table)</li>
</ul>
<p><em>Written by Faisal, MEP engineer with 16+ years in building services design and shop drawings. Updated October 2026.</em></p>
<p><em>Disclaimer: This article and the linked calculator provide preliminary engineering estimates. Final pump selection must be verified against manufacturer performance curves and applicable codes.</em></p>
<p><script type="application/ld+json">
{
  "@context": "https://schema.org",
  "@type": "FAQPage",
  "mainEntity": [
    {"@type": "Question", "name": "How do you calculate boiler feed pump capacity?", "acceptedAnswer": {"@type": "Answer", "text": "Multiply the boiler's maximum evaporation rate by 1.15-1.25, then divide by water density at feedwater temperature to convert kg/hr to m3/hr. The margin covers blowdown, feed-control cycling and safety-valve lift."}},
    {"@type": "Question", "name": "How much head does a boiler feed pump need?", "acceptedAnswer": {"@type": "Answer", "text": "Take the safety-valve set pressure plus about 3% accumulation, add the economizer and feed-valve pressure drops, subtract any pressure in the feed tank or deaerator, and convert to metres of water (about 10.2-10.7 m per bar depending on temperature). Then add the static height from tank level to boiler inlet and the pipe friction."}},
    {"@type": "Question", "name": "Why is the feed pump sized at 1.25 times evaporation?", "acceptedAnswer": {"@type": "Answer", "text": "Because the pump must refill the boiler faster than steam leaves it, replace blowdown water, and hold drum level even while the safety valve is lifting. Boiler codes require feed capacity above peak evaporation."}},
    {"@type": "Question", "name": "How do you calculate NPSH for a boiler feed pump?", "acceptedAnswer": {"@type": "Answer", "text": "NPSH available = (absolute pressure on the tank surface - vapour pressure at feedwater temperature) / (density x g), plus the height of the water level above the pump, minus suction pipe friction. For a deaerator at saturation the pressure term is zero, so the NPSH comes only from elevation."}},
    {"@type": "Question", "name": "What type of pump is used for boiler feed water?", "acceptedAnswer": {"@type": "Answer", "text": "Vertical or horizontal multistage centrifugal pumps, because of the high head requirement. Typical efficiency at small feed duties is 35-65%. Very small boilers sometimes use regenerative turbine pumps."}},
    {"@type": "Question", "name": "What is the formula for pump motor power?", "acceptedAnswer": {"@type": "Answer", "text": "P (kW) = density x g x Q x H / (3.6 x 10^6 x efficiency), where Q is in m3/hr, H in metres and density in kg/m3. Then select the next standard IEC motor rating above P x (1 + service factor)."}}
  ]
}
</script></p>
]]></content:encoded>
					
					<wfw:commentRss>https://mepbase.com/boiler-feed-pump-calculation/feed/</wfw:commentRss>
			<slash:comments>0</slash:comments>
		
		
			</item>
	</channel>
</rss>
